Short-circuit inductance

Measurement of short-circuit inductance

Short-circuit inductance of a real linear two-winding transformer is inductance measured across the primary or secondary winding when the other winding is short-circuited.[1][Notes 1]  The method of measuring the short circuit inductance is described in industrial standard. The industrial standard also stipulates a method for obtaining the coupling factor by combining it with the open circuit inductance value.

Equivalent circuit

Measured primary and secondary short-circuit inductances may be considered as constituent parts of primary and secondary self-inductances. They are derived by using Ho-Thevenin's theorem from the equivalent inductance of the three-terminal equivalent circuit as follows. Then they are related according to the coupling factor as,

L s c 1 = ( 1 k 2 ) L 1 {\displaystyle L_{\mathrm {sc1} }=(1-k^{2})\cdot L_{\mathrm {1} }\,}
L s c 2 = ( 1 k 2 ) L 2 {\displaystyle L_{\mathrm {sc2} }=(1-k^{2})\cdot L_{\mathrm {2} }\,}

Where

  • k is coupling coefficient
  • L1 is primary self-inductance
  • L2 is secondary self-inductance

Short-circuit inductance measurement is used in conjunction with open-circuit inductance measurements to obtain various derived quantities like k {\displaystyle k} , the inductive coupling factor and σ {\displaystyle \sigma } , the inductive leakage factor. k {\displaystyle k} is derived according to:[Notes 2]

k = 1 L sc L oc {\displaystyle k={\sqrt {1-{\frac {L_{\text{sc}}}{L_{\text{oc}}}}}}}

where

  • L sc {\displaystyle L_{\text{sc}}} is the short-circuit measurement of primary or secondary inductance
  • L oc {\displaystyle L_{\text{oc}}} is the corresponding open-circuit measurement of primary or secondary inductance

Other transformer parameters like leakage inductance and mutual inductance which cannot be directly measured may be defined in terms of k.

Short-circuit inductance is one of the parameters that determines the resonance frequency of the magnetic phase synchronous coupling in a resonant transformer and wireless power transfer. Short-circuit inductance is the main component of the current-limiting parameter in leakage transformer applications.

See also

  • Resonant inductive coupling

References

  1. ^ Japan Industrial Standard C 5602-1986, pp 34, 4305

Notes

  1. ^ This value is sometimes imprecisely referred to as leakage inductance
  2. ^ the same k value can be obtained measured from the primary side or from the secondary side